Refractory Installation Quality Control— Inspection and Testing of AES/RCF Linings and Materials. Our API 936 Refractory Personnel bank draws 265 of its 1,848 questions from this publication — 14% — and they cite 127 different clauses. The clause list below is counted from those questions, not copied from a syllabus.

Clauses the questions cite

The 40 most cited of 127, in document order. The number is how many questions in our bank reference that clause.

3.1 · 23.2 · 13.3 · 13.4 · 23.5 · 13.7 · 33.8 · 13.10 · 13.12 · 13.13 · 13.14 · 13.15 · 13.17 · 13.18 · 13.19 · 13.21 · 13.22 · 13.24 · 13.25 · 23.26 · 13.27 · 13.28 · 13.29 · 13.30 · 13.31 · 23.32 · 13.33 · 13.35 · 23.36 · 13.37 · 23.38 · 13.39 · 13.40 · 13.41 · 23.42 · 13.43 · 23.44 · 13.45 · 13.46 · 23.47 · 1

What they ask about

Installer responsibilities 11Terminology - 976-MATL 11Lining Design - 976-QC 10Lining Design - 976-MATL 9Owner responsibilities 6Lining Design Scenario - 976-MATL 6Inspector responsibilities 5Hammer/bend test 4Workmanship - 976-QC 4Workmanship Scenario - 976-QC 4Scope 3Inspector qualifications 3Anchor materials 3Module installation 3

Free sample questions from API 976

  1. A vapor barrier is installed with edges overlapped by 100 mm and a small puncture left unsealed. Identify the errors.

    • A. Two errors: overlap shall be at least 175 mm, and punctures shall be sealed ✓
    • B. No error; 100 mm overlap is sufficient
    • C. One error: the overlap only
    • D. One error: the puncture only
    • E. Two errors: overlap shall be 254 mm, and foil shall be aluminium for that stage

    Vapor barrier edges shall be overlapped by at least 175 mm, and edges and punctures shall be overlapped and sealed with sodium silicate, fiber cement, mortar, or moldable. A barrier with an unsealed puncture gives no protection at that point. API 976, 8.2

  2. What are the requirements for a blanket hot-face layer in layered construction?

    • A. Needled blanket 12 mm thick at 64 kg/m3 density
    • B. Any blanket 50 mm thick at 96 kg/m3 density
    • C. Needled blanket 25 mm thick at 128 kg/m3 density ✓
    • D. Vacuum formed board at 38 mm thickness and 240 kg/m3 nominal density
    • E. Wet blanket 25 mm thick at any density

    In layered construction the hot-face layer shall be a needled blanket 25 mm (1 in.) thick at 128 kg/m3 (8 lb/ft3) density, for both overlap and butt joint construction. The 38 mm at 240 kg/m3 figures belong to fiberboard used as a hot face, and 96 kg/m3 is the minimum for backup blanket. API 976, 8.2

All free API 936 Refractory Personnel questions

Other publications in this exam

1,848 API 936 Refractory Personnel questions

Counts are from AssetronX’s own question bank and describe what we have written, not what the exam contains. AssetronX is an independent examination-preparation provider and is not affiliated with, endorsed by or accredited by any certifying body or standards organisation. The clause numbers refer to the publications’ own paragraphs; the publications themselves are not reproduced here.